1SKC000006C0201
3/44
Automation Technologies
FBP FieldBusPlug
Survey - Device Data Overview
MSD11-FBP
MSR22-FBP
MFI21-FBP
UMC22-FBP
ASD11-FBP
(AS interface)
ASP22-FBP
(AS interface)
PDP22-FBP
(Profibus DP)
DNP22-FBP
(DeviceNet)
FieldBusPlug terminal devices FieldBusPlug Full usability of terminal device Remarks
FieldBusPlug bus connectors terminal devices functions with FieldBusPlug ...
For detailed technical
information please
Functions and technical data refer to the FieldBusPlug
system documentation
Features
Usage without fuse protection x x x see data sheet in FBP document.
Switching frequency
x x
max. 15 starts/h, max. 60 starts/h
(motor starting) at 40% duty ratio, start. time = 1 s
Fuse on line side required x
Operating voltage 400 V 690 V AC, 50 and 60 Hz
Control voltage 24 V DC (+ 30%, - 20%)
Current range up to max. 12 A 63 A
Curr. range with MS325 up to max. 25 A
Integrated motor control functions
Direct starting x x x x x x x
Reverse starting x x x x x x
Positioner x x x
Star-delta starting x x x x x
Transparent mode x x x x
Integrated motor monitoring
Short-circuit, overload x x power path is switched off
Overload, phase failure x trip category 5, 10, 20, 30
Integrated inputs and outputs
3 digital inputs x x x x 24 V DC
6 digital inputs x x x 24 V DC
1 additional digital input x x x x mechanical coupling with MS325
3 digital relay outputs x x x x x 250 V AC, 24 V DC, 2 A max.
Integrated diagnostic functions
LED supply voltage x x x x x x x x green
LED switch pos. contactor(s) x x yellow
LED switch pos. motor protection x x yellow
LED bus failure x x x x red
LED function failure x x x x x x x red
LED motor running x yellow
LED for states of digital I/Os x x yellow
Bus info contactors x x x x x x x x Information to PLC
Bus info motor protection x x x Information to PLC
Bus info motor current x x x Information to PLC
Bus info switching cycles count x x x x Information to PLC
Parameter settings
Change-over time via potentiometer x fixed basic time 50 ms
Change-over time via operat. panel x fixed basic time 50 ms
Change-over time via PLC program x x x x fixed basic time 50 ms
Motor current x x x x x x x at the motor protecting switch
Motor current, trip category x x x x optional operating panel
Motor current, trip category x x x PLC program
Mounting
Mounting on DIN rail x x x x 35 mm DIN rail
Mounting on 2 DIN rails x x increased vibration resistance
Mounting by screws x 4 screws M4
Connections and conductor cross sections
Connecting terminals x x x x 1 x 2.5 or 2 x 1.5 mm
2
max.
PE tapping directly on DIN rail x x to motor connecting plug
Bus connection via FBP conn. x x x x x x x x
Bushing-type transformer x 25 mm
2
max. (diameter 11 mm)
Ambient conditions
Degree of protection IP20 IP 20 IP65
Storage temp. - 40 ... + 80°C x x x x x x x x
Operating temp. 0 ... + 55°C x x x x x x x x
Approvals
CE, UL, CSA, GL, BV, LRS x x x x x x x x partly in preparation