1SKC000006C0201
3/41
Automation Technologies
FieldBus Plug
FBP FieldBusPlug
Survey - FBP Terminal Device Data
Motorstarter Direct
MSD11-FBP
Motorstarter Reverse
MSR22-FBP
Communicative motor starters - compact devices
Dimensions 45 x 260 x 120 (138) mm
Mounting DIN rail, on 1 or 2 rails as desired (spacing 125 mm),
usage of 2 rails increases vibration resistance
Optional Woehner conductor rail system adapter, Rittal, Germany
Degree of protection IP 20
Power feeding Comb-shaped rail or cable
Operating voltage V
i
400 V AC, 50 and 60 Hz, three-phase current
Control voltage feeding Simplest feeding via bus connector; switchable to ext. feeding
External attachment plug 1.5 mm
2
max. (supplied on delivery)
Control voltage 24 V DC (+ 30%, - 20%)
Motor connection Plug-in conn. on front-side (plug supplied on del.) L1, L2, L3, PE
Conductor cross section 2.5 mm
2
max.
Motor protection Integr. motor protecting switch MS116 (overload, short-circuit)
Conductor cross section 2 x 1...4 mm
2
(single- or multiple-wire)
2 x 0.75...2.5 mm
2
(fine-wire with wire-end ferrules)
Nominal current ranges 11
Applicability 0.1...12 A
Short-circuit capacity ICS 50 kA (0.1 - 6.3 A), 12.5 kA (6.3 - 10 A), 10 kA (10 - 12 A)
Switching frequency max. 15 starts per hour
(motor starting) max. 60 starts per hour at 40 % duty ratio and t
starting
= 1 s
Contactor Integrated contactor B7
Contact rating 12 A max., AC-3, 400 V AC
Contact lifetime 700,000 switching cycles at 12 A, AC-3
Integrated diagnostic functions LED for control voltage
LED for contactor switch position
LED for motor protection
Dimensions 45 x 260 x 120 (150) mm
Mounting DIN rail, on 1 or 2 rails as desired (spacing 125 mm),
usage of 2 rails increases vibration resistance
Optional Woehner conductor rail system adapter, Rittal, Germany
Degree of protection IP 20
Power feeding Comb-shaped rail or cable
Operating voltage V
i
400 V AC, 50 and 60 Hz, three-phase current
Control voltage feeding Simplest feeding via bus connector; switchable to ext. feeding
External attachment plug 1.5 mm
2
max. (supplied on delivery)
Control voltage 24 V DC (+ 30%, - 20%)
Motor connection Plug-in conn. on front-side (plug supplied on del.) L1, L2, L3, PE
Conductor cross section 2.5 mm
2
max.
Motor protection Integr. motor protecting switch MS116 (overload, short-circuit)
Conductor cross section 2 x 1...4 mm
2
(single- or multiple-wire)
2 x 0.75...2.5 mm
2
(fine-wire with wire-end ferrules)
Nominal current ranges 11
Applicability 0.1...12 A
Short-circuit capacity ICS 50 kA (0.1 - 6.3 A), 12.5 kA (6.3 - 10 A), 10 kA (10 - 12 A)
Switching frequency max. 15 starts per hour
(motor starting) max. 60 starts per hour at 40 % duty ratio and t
starting
= 1 s
Contactor Integrated contactor 2 x B7
Contact rating 12 A max., AC-3, 400 V AC
Contact lifetime 700,000 switching cycles at 12 A, AC-3
Integrated diagnostic functions LED for control voltage
LED for contactors switch positions
LED for motor protection